6135HF475 13.5L Generator Drive Engine

6135HF475 13.5L Generator Drive Engine

Overview

  • PowerTech™ E
  • Standby: 330-460 kW (442-616 hp) @ 1800 rpm
  • Prime: 300-418 kW (402 - 560 hp) @ 1800 rpm
Request A Quote
Features

Features

Expand All Collapse All

FIXED GEOMETRY TURBOCHARGER

  • Fixed geometry turbochargers are precisely matched to the power level and application

4-VALVE CYLINDER HEAD

  • Provides excellent airflow resulting in better transient response
  • Cross-flow design

AIR-TO-AIR AFTERCOOLED

  • Most efficient method of cooling intake air to help reduce engine emissions while improving transient response time
  • Enables an engine to meet emissions with better fuel economy and the lowest installed costs

EUI FUEL SYSTEM

  • Electronic unit injector (EUI) fuel system provides variable common rail pressure, multiple injections, and higher injection pressures up to 2,000 bar (29,000 psi). It also controls fuel injection timing and provides precise control for start, duration, and end of injection

JOHN DEERE ELECTRONIC ENGINE CONTROLS

  • Electronic engine controls monitor critical engine functions, providing warning and/or shutdown to prevent costly repairs and eliminate the need for add-on governing components, all lowering total installed costs.

Specifications

Emissions certifications

EPA Tier 2
EU Stage II

General engine data

Model 6135HF475
Number of cylinders 6
Displacement-- L (cu in) 13.5 (824)
Bore and Stroke-- mm (in) 132 x 165 (5.20 x 6.50)
Compression Ratio 16.0 : 1
Engine Type In-line, 4-Cycle
Aspiration Turbocharged and air-to-air aftercooled
Length - mm (in) 1362 (53.6)
Width-- mm (in) 857 (33.7)
Height-- mm (in) 1210 (47.6)
Weight, dry - kg (lb) 1334 (2941)

Performance data range

Hz (rpm) 60 ( 1800 )
50 ( 1500 )
Generator Efficiency % 90-95
90-93
Power Factor 0.8
0.8
Engine power - Prime kW 300-410
323-415
Engine power - Prime hp 402-550
433-556
Engine power - Standby kW 330-460
355-456
Engine power - Standby hp 443-617
476-612
Rated Fan Power - kW 19.8-27.6
17.8-22.8
Rated Fan Power - hp 26.6-37.0
23.9-30.6
Calculated generator set output - Prime kWe 254-373
276-367
Calculated generator set output - Prime kVA 317-467
345-458
Calculated generator set output - Standby kWe 279-411
304-403
Calculated generator set output - Standby kVA 349-513
379-504